Skip to main content
Siemens 5SU9304-0KK40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9304-0KK40 SENTRON RCBO, 40A, 10kA, B-Curve, 30mA

MPN5SU9304-0KK40
Active

Siemens SENTRON RCBO, 10 kA, 1P+N, Type AC, 30 mA, B char., In: 40 A, Un AC: 230 V, pigtail 600 mm, solid N.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9304-0KK40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9304-0KK40 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9304-0KK40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm
5SU9304-0KK40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9304-0KK40 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU9304-0KK40 is a SENTRON RCBO — an RCD-operated circuit breaker combining overcurrent and residual-current protection in one 18 mm-wide module. It's rated 40 A with a B-curve trip characteristic and 30 mA Type AC residual sensitivity, breaking capacity 10 kA per EN 60898 and IEC 60947-2. The 1P+N design protects one live pole while switching the neutral, and the 600 mm pigtail with solid neutral simplifies wiring in distribution boards.

The B-curve (3-5 In magnetic trip) is the default for general-purpose socket circuits and lighting; it avoids nuisance tripping from inrush on resistive loads while still clearing fast on hard shorts. At 18 mm width (1 modular unit), it occupies one DIN-rail position — critical when backfilling an existing board where every slot counts. The 30 mA Type AC residual sensitivity catches sinusoidal AC earth faults — the most common type in domestic and office wiring. It's not suitable for pulsating DC or smooth DC fault currents (Type A or F would be needed for EV chargers, VFD-fed circuits, or three-phase rectifier loads).

Mounts in any position on standard DIN rail. The 1 MW width occupies one position. The -40 °C to +75 °C ambient range covers unheated utility rooms and outdoor enclosures in temperate climates.

Frequently asked questions

What is the closest functional second-source to 5SU9304-0KK40?

The 5SY6040-6 is a Siemens MCB (overcurrent only) with similar 40 A B-curve rating and 1 MW width, but it lacks the integrated RCD function. The 5SU9304-0KK40 is an RCBO — it combines overcurrent and 30 mA residual-current protection in one unit. If your design needs the combined protection, the 5SY series alone won't drop in without adding a separate RCCB.