Skip to main content
Siemens 5SU9304-6PK50 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9304-6PK50 SENTRON RCBO, 40 A, 30 mA, B Curve, 10

MPN5SU9304-6PK50
Active

Siemens SENTRON RCBO, 1P+N, 40 A, 30 mA Type A, B characteristic, 10 kA, 230 V AC, 1 MW width.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU9304-6PK50 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU9304-6PK50 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SU9304-6PK50 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU9304-6PK50 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU9304-6PK50 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU9304-6PK50 is a SENTRON RCBO — a combined residual-current device and miniature circuit breaker in one 18 mm wide module. It protects a single-phase final subcircuit against overload, short-circuit, and earth leakage in one package, saving a DIN rail position compared to separate RCD and MCB. Rated 40 A at 30 °C with B-curve tripping characteristic. 30 mA Type A residual current element catches sinusoidal AC and pulsating DC faults. Breaking capacity is 10 kA per both EN 60898 and IEC 60947-2, meaning it can safely interrupt fault currents up to that level at 230 V AC without welding contacts or cascading upstream. That covers most commercial and light industrial distribution boards; for higher fault levels you'd step to a higher-rated upstream device.

Mounting and integration

Snaps onto standard 35 mm DIN rail, occupies one modular width (18 mm). Depth is 77 mm, installation depth 70 mm — check gland-plate clearance if the enclosure is shallow. Mounting position is unrestricted, and the supply can enter from top or bottom, which simplifies busbar routing in a crowded panel. Degree of pollution 2, overvoltage category III — rated for fixed-installation distribution boards where transient overvoltages are controlled by upstream SPDs. IP20 with the distribution board installed and conductors connected; not for wet or washdown environments.

Frequently asked questions

What does the 30 mA Type A residual current rating mean?

It trips on sinusoidal AC faults and on pulsating DC faults (e.g., from half-wave rectifiers in electronics or VFDs). Type A is the standard requirement for circuits feeding modern appliances and IT equipment.

MPN
5SU9304-6PK50