Siemens 5SU9304-7KX20 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9304-7KX20 SENTRON RCBO, 20 A, Type A, 10 kA

MPN5SU9304-7KX20
Active

Siemens SENTRON 5SU9304-7KX20, RCBO, 2-pole 1P+N, 20 A, C-curve, Type A, 10 kA, 18 mm width, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU9304-7KX20 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU9304-7KX20 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SU9304-7KX20 — Mechanical
ParameterValue
Mounting positionany
Maximum4.36 W
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU9304-7KX20 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors, IP40 is achieved

Electrical

5SU9304-7KX20 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What it is and what it does

The Siemens 5SU9304-7KX20 is a SENTRON RCBO — an RCD-operated circuit breaker combining overcurrent protection and residual current detection in a single 18 mm wide module. It's rated 20 A at 30 °C with a C tripping characteristic, Type A fault current sensitivity, and a 10 kA breaking capacity certified to both EN 60898 and IEC 60947-2. That dual certification means it's accepted across residential, commercial, and light industrial panel builds where the local standard may reference either norm. Type A detection handles pulsating DC residual currents up to 6 mA superimposed on AC — common from rectified loads like LED drivers, switched-mode power supplies, and variable-speed drives. If your panel feeds any electronics, Type A is the correct choice over Type AC.

Thermal derating and real-world current

The 20 A rating holds at 30 °C ambient. Above that, the continuous current must be derated: 19 A at 40 °C, 18.2 A at 45 °C, 17.6 A at 50 °C, and 17.2 A at 55 °C. If the panel interior runs hot — and most enclosed panels do — size the load circuit for the derated value at your expected ambient, not the headline 20 A.

Mounting and wiring constraints

The 18 mm width (1 width unit) fits standard DIN-rail enclosures. Installation depth is 70 mm, overall depth 77 mm — check the enclosure depth before committing; a shallow 80 mm box leaves only 3 mm clearance for wiring. Accepts solid or stranded conductors from 0.75 to 35 mm², which covers everything from lighting circuits to sub-main feeders. Mounting position is any orientation, so it works in vertical or horizontal busbar arrangements without derating.

Compliance and approvals

Rated for overvoltage category III, protection class IP20 (IP40 with connected conductors in a distribution board), halogen-free and silicon-free construction. The 10 kA breaking capacity is listed under both EN 60898 and IEC 60947-2, covering the two main MCB/RCBO standards globally. Touch protection is included on the terminals.

Frequently asked questions

What is the breaking capacity of 5SU9304-7KX20?

10 kA rated breaking capacity, certified to both EN 60898 and IEC 60947-2.

What conductor sizes does 5SU9304-7KX20 accept?

Solid or stranded conductors from 0.75 to 35 mm².

Where can I buy 5SU9304-7KX20 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation is available for 5SU9304-7KX20?

The part carries dual certification to EN 60898 and IEC 60947-2 for breaking capacity, is halogen-free and silicon-free, and is rated overvoltage category III.