Siemens 5SU9306-0KK10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9306-0KK10 SENTRON RCBO, 10A, B-curve, 6kA, 1P+N

MPN5SU9306-0KK10
Active

Siemens SENTRON 5SU9 series RCBO, RCD-operated circuit breaker, 10 A, B-characteristic, 6 kA, 1P+N, 18 mm wide.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9306-0KK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9306-0KK10 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9306-0KK10 — Mechanical
ParameterValue
Mounting positionany
Maximum0.75 W
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm
5SU9306-0KK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9306-0KK10 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU9306-0KK10 is a 1P+N RCD-operated circuit breaker from the SENTRON 5SU9 series — a combined overcurrent and residual current device (RCBO) that fits a single 18 mm width unit on the DIN rail. It's rated 10 A with a B tripping characteristic, meaning it trips between 3 and 5 times rated current for fast magnetic release on short circuits, and it handles fault currents up to 6 kA per EN 60898 and IEC 60947-2.

Above that, the continuous current must be derated: 9.4 A at 40 °C, 9.1 A at 45 °C, 8.7 A at 50 °C, and 8.1 A at 55 °C. If the distribution board runs warm — common in a crowded enclosure — factor the actual load against the derated figure, not the 30 °C headline number.

Wiring and installation

Terminals accept solid or stranded conductors from 0.75 mm² up to 35 mm² — covers everything from 1.5 mm² lighting circuits up to 10 mm² submain tails. Touch protection is built in.

Frequently asked questions

What is the breaking capacity of this RCBO?

6 kA rated value per EN 60898 and IEC 60947-2, which covers the majority of domestic and light commercial final-circuit fault levels.

What conductor sizes does the 5SU9306-0KK10 accept?

Solid or stranded conductors from 0.75 mm² up to 35 mm².

Where can I buy the 5SU9306-0KK10?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.