Skip to main content
Siemens 5SU9326-1CN06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9326-1CN06 SENTRON RCBO, 6A C-curve, 6kA, 2P

MPN5SU9326-1CN06

Siemens SENTRON 5SU9326-1CN06, RCBO, 2-pole, 6 A, C-curve, 6 kA, 4 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SU9326-1CN06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9326-1CN06 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9326-1CN06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum75 °C
Minimum-40 °C
Width72 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9326-1CN06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9326-1CN06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Panel fit and installation

At 72 mm wide (4 MW), 90 mm tall, and 77 mm deep (70 mm installation depth), this RCBO snaps onto a DIN rail in any mounting position. The IP20 rating applies once the distribution board is installed with conductors connected — so it's a panel-interior device, not a standalone enclosure. Supply can come from top or bottom, which saves a few minutes when you're retrofitting into an existing board and the busbar layout is already set.

Temperature derating — the real-world rating

At 40 °C it derates to 5.3 A, at 45 °C to 5.2 A, at 50 °C to 4.9 A, and at 55 °C to 4.6 A.

Material compliance and approvals

The surge voltage resistance is rated at 4 kV, and it handles a 1 kA surge current (8/20 μs waveform). Compliance documentation (RoHS, REACH, CE) is standard with the brand; the UL/CSA listing is not stated in the evidence, so verify if a North American approval mark is required for your jurisdiction.

MPN