5SU9326-1CS10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9326-1CS10 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9326-1CS10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum75 °C
Minimum-40 °C
Width72 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9326-1CS10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9326-1CS10 — Electrical
ParameterValue
Tripping Characteristic ClassC
Operational current / at AC / rated value10 A

Product details

What this RCBO carries

The Siemens 5SU9326-1CS10 is a 2-pole RCBO from the SENTRON family — a combined residual-current device and miniature circuit breaker in one 4-module-width unit. It breaks fault currents up to 6 kA per EN 60898 and IEC 60947-2, trips on residual currents of 30 mA (Type AC, meaning it detects sinusoidal AC earth faults), and follows a C tripping characteristic for moderate inrush loads like motor starters and lighting banks. Rated 10 A at 400 V AC, it also includes integrated overvoltage protection set at 280 V, which clamps the line-to-neutral voltage before surge damage reaches downstream equipment.

Panel fit and environmental range

Snaps onto DIN rail, occupies 4 modular width units (72 mm wide), with a depth of 77 mm and an installation depth of 70 mm. Operating temperature spans -40 °C to 75 °C, with max 95% humidity. Halogen-free and silicon-free construction, so it won't outgas corrosive compounds in sealed enclosures or near sensitive contacts.

Frequently asked questions

What is the closest functional second-source to 5SU9326-1CS10?

The 5SL6550-7BB is a peer RCBO from the same SENTRON family, but it differs in poles and rating — verify your specific voltage and current requirements before substituting. The 5SU9326-1CS10 carries 2 poles, 10 A, C-curve, 30 mA Type AC, with overvoltage protection at 280 V.

Will 5SU9326-1CS10 drop into a panel specified around 5SL6550-7BB without rewiring?

Both are 4-module-width DIN-rail devices (72 mm wide), so the mechanical footprint is the same. However, the 5SU9326-1CS10 is a 2-pole RCBO with overvoltage protection, while the 5SL6550-7BB may differ in poles, rating, or features — always compare the wiring diagram and rated parameters before direct swap.