Siemens 5SU9346-1CR32 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9346-1CR32 SENTRON RCBO, 32A, 30mA, Type AC, 6kA

MPN5SU9346-1CR32

Siemens SENTRON 5SU9346-1CR32, RCBO, 4-pole, 32 A, 30 mA, type AC, 6 kA, C-curve, 7 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU9346-1CR32 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SU9346-1CR32 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9346-1CR32 — Mechanical
ParameterValue
Mounting positionany
Width in modular units7
Maximum75 °C
Minimum-40 °C
Width126 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9346-1CR32 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9346-1CR32 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What this RCBO does in the panel

The Siemens 5SU9346-1CR32 is a 4-pole RCBO (residual-current-operated circuit breaker with overcurrent protection) from the SENTRON family, combining a 32 A thermal-magnetic trip (C-curve) with a 30 mA type AC residual-current device in one 7-module-wide unit. The 30 mA trip threshold protects against direct-contact shock risk in standard AC circuits (sinusoidal residual currents only — not pulsed DC or smooth DC, which is the type AC limitation).

Thermal derating — the real-world current limit

At 30 °C ambient the device carries its full 32 A. At 40 °C it derates to 29.8 A; at 45 °C to 28.5 A; at 50 °C to 27.8 A; at 55 °C to 27.2 A. If the distribution board runs warm — common in a packed enclosure — the continuous load must stay below the derated value. The C-curve (magnetic trip at 5–10× In) handles motor inrush and transformer energization without nuisance tripping, but the thermal element follows the derating table.

Width is 126 mm (7 modular width units). Height is 90 mm.

Coordination and selectivity context

Energy limitation class 3 limits let-through energy for downstream cable protection. The 4 kV rated surge voltage matches overvoltage category III requirements. Insulation voltage is 440 V.