Skip to main content
Siemens 5SU9346-1CR63 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU9346-1CR63 RCD Circuit Breaker, 63 A, 4P,

MPN5SU9346-1CR63

Siemens SENTRON 5SU9346-1CR63, RCD-operated circuit breaker, 4-pole, 63 A (30 °C), C characteristic, 6 kA (EN 60898), 400 V AC, 7 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SU9346-1CR63 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SU9346-1CR63 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9346-1CR63 — Mechanical
ParameterValue
Mounting positionany
Width in modular units7
Maximum75 °C
Minimum-40 °C
Width126 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9346-1CR63 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9346-1CR63 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

RCD-operated circuit breaker — 4-pole, 63 A, C curve

The Siemens SENTRON 5SU9346-1CR63 is an RCD-operated circuit breaker — a combined residual-current device and overcurrent protection in one 4-pole unit. It carries a 63 A rating at 30 °C (derated to 58.6 A at 40 °C, 56.1 A at 45 °C, 54.8 A at 50 °C, and 53.6 A at 55 °C) with a C tripping characteristic, meaning it handles moderate inrush from motor or transformer loads without nuisance trips. Rated AC operating voltage of 400 V, insulation voltage (Ui) 440 V, overvoltage category III, pollution degree 2 — standard for fixed-installation switchgear. The instantaneous design (no intentional time delay on the RCD function) provides fast disconnection for earth faults. Supply can enter from either top or bottom; mounting position is unrestricted.

Occupies 7 modular width units (MW) on a DIN rail. Overall dimensions: 126 mm wide, 90 mm high, 77 mm deep (installation depth 70 mm). Halogen-free and silicon-free construction suits clean-room or low-smoke installations.

Frequently asked questions

When sourcing 5SU9346-1CR63, what's the closest functional second-source — 5SL4363-7?

The 5SL4363-7 is a standard MCB (overcurrent only) without the integrated RCD function. The 5SU9346-1CR63 combines RCD and overcurrent protection in one unit. They are not drop-in substitutes; the 5SU9346-1CR63 is the correct choice if residual-current protection is required in the same device.

What is 5SU9346-1CR63's listed depth (77 mm) on this component line?

The overall depth is 77 mm; the installation depth (behind the panel face) is 70 mm.

What is 5SU9346-1CR63's listed width (126 mm) on this component line?

Width is 126 mm, which corresponds to 7 modular width units on a standard DIN-rail mounting system.

Will 5SU9346-1CR63 drop into a panel that was specified around 5SL4363-7 without rewiring?

No. The 5SL4363-7 is a 4-pole MCB with no RCD function; the 5SU9346-1CR63 is an RCBO (RCD + MCB). The wiring and neutral bus arrangement differ because the RCBO requires a neutral connection through the device. Panel rework is needed.

MPN
5SU9346-1CR63