Skip to main content
Siemens 5SU9354-7KK25 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9354-7KK25 SENTRON RCBO, 25 A, 30 mA, Type A, C

MPN5SU9354-7KK25
Active

Siemens SENTRON 5SU9354-7KK25, RCD-operated circuit breaker, 1P+N, 25 A, 30 mA, Type A, tripping characteristic C, 10 kA, 2 MW.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9354-7KK25 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9354-7KK25 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9354-7KK25 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9354-7KK25 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9354-7KK25 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9354-7KK25 is a SENTRON RCD-operated circuit breaker — an RCBO combining overcurrent and residual-current protection in a single 2-module-width (36 mm) package. Rated 25 A at 30 °C with a 30 mA residual-current trip, Type A, characteristic C, and a 10 kA breaking capacity per EN 60898 and IEC 60947-2. This is a 1P+N unit (switched phase, solid neutral), designed for instantaneous fault clearing.

The 25 A rating at 30 °C is the headline current; derate to 23.5 A at 40 °C, 22.75 A at 45 °C, 21.75 A at 50 °C, and 20.25 A at 55 °C.

Mounting position any, supply feed from top or bottom. IP20 with conductors connected and panel closed, so it's for indoor, dry, pollution-degree-2 environments (normal residential or commercial panels). Overvoltage category III means it's rated for fixed-installation downstream of the service entrance.

Marked as current production. This is not an NRND or obsolete line — the SENTRON RCBO family remains active in Siemens' catalog. No official successor exists because none is needed.

Frequently asked questions

What are the key ratings of 5SU9354-7KK25?

25 A rated current (derated at elevated temperatures), 30 mA Type A residual current, C characteristic, 10 kA breaking capacity per EN 60898 and IEC 60947-2, 1P+N, 2 MW (36 mm wide).

Will 5SU9354-7KK25 fit a panel designed around 5SL6550-7BB?

No — they are different form factors. The 5SU9354-7KK25 is a 2-MW (36 mm wide) RCBO; the 5SL6550-7BB is a 1-MW MCB. The 5SU9354-7KK25 is wider and includes residual-current protection the 5SL6550-7BB lacks. Panel cutouts and busbar positions would need adjustment.

Where can I buy 5SU9354-7KK25 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SU9354-7KK25