Skip to main content
Siemens 5SU9354-7KK63 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU9354-7KK63 RCBO, 63 A C-curve, 10 kA, 1P+

MPN5SU9354-7KK63
Active

Siemens SENTRON RCBO, 5SU9354-7KK63, 63 A rated at 30 °C, C-curve, 10 kA breaking capacity (EN 60898 / IEC 60947-2), 1P+N, 2 modular widths, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9354-7KK63 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9354-7KK63 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9354-7KK63 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9354-7KK63 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9354-7KK63 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU9354-7KK63 is a 1P+N RCD-operated circuit breaker (RCBO) combining overcurrent and residual-current protection in a single 2-module-wide (36 mm) package. Rated 63 A at 30 °C with a C-curve tripping characteristic, it breaks fault currents up to 10 kA per EN 60898 and IEC 60947-2.

At 40 °C it derates to 59.22 A, at 45 °C to 57.33 A, at 50 °C to 54.81 A, and at 55 °C to 51.03 A. For a panel running warm — typical near a transformer or drive cabinet — size the load against the derated figure, not the 30 °C headline.

Panel integration

Snaps onto DIN rail (EN 60715) in any mounting position. Two modular widths (36 mm) and 77 mm depth fit standard distribution boards.

Frequently asked questions

What is the breaking capacity of 5SU9354-7KK63?

10 kA per both EN 60898 and IEC 60947-2, at 230/240 V AC.

What is the width and depth of this RCBO?

Width is 36 mm (2 modular units), depth is 77 mm.

Where can I buy 5SU9354-7KK63?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
5SU9354-7KK63