Siemens 5SU9356-1CN63 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-1CN63 SENTRON RCBO, 63A C-Curve 30mA 6kA

MPN5SU9356-1CN63

Siemens SENTRON 5SU9356-1CN63, RCBO, 2-pole, 63 A rated, C tripping characteristic, 30 mA residual current, 6 kA breaking capacity, instantaneous design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU9356-1CN63 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU9356-1CN63 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SU9356-1CN63 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU9356-1CN63 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU9356-1CN63 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Siemens 5SU9356-1CN63 — RCBO for 63 A final circuits

The Siemens 5SU9356-1CN63 is a 2-pole residual-current-operated circuit breaker (RCBO) from the SENTRON series, combining overcurrent and earth-fault protection in a single 36 mm-wide (2 MW) DIN-rail module. It is rated 63 A at 30 °C with a C tripping characteristic and a 30 mA residual-current trip, making it the primary choice for general-purpose socket-outlet circuits and mixed resistive-inductive loads in commercial and residential distribution boards where both overload and residual-current protection are required in one device.

Rated current and thermal derating

The 63 A rating holds at 30 °C ambient. At 40 °C it derates to 58.6 A, at 45 °C to 56.1 A, at 50 °C to 54.8 A, and at 55 °C to 53.6 A — a 15 % drop from the 30 °C figure. If the panel ambient runs above 40 °C, the continuous load must be sized against the derated value, not the nameplate 63 A, to avoid nuisance tripping in sustained operation.

Mounting and integration

Mounts on standard DIN rail in any position. The 36 mm width (2 modular units) and 77 mm depth fit standard distribution board cutouts; installation depth is 70 mm.

Residual current type and design

The residual-current element is Type AC — it detects sinusoidal AC earth-fault currents only. For circuits with pulsed DC or smooth DC fault components (e.g., variable-speed drives, UPS systems, LED drivers), a Type A or Type B RCD would be required. The design is instantaneous (no intentional time delay), so it trips within the standard RCD response time on a 30 mA fault. This is suitable for general socket-outlet protection but not for selectivity with upstream delayed RCDs.

MPN