Siemens 5SU9356-1CR20 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-1CR20 SENTRON RCBO, 20A Type C, 30mA, 6kA

MPN5SU9356-1CR20

Siemens SENTRON RCBO, 1P+N, 20 A, Type C, 30 mA, 6 kA, 2 MW, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9356-1CR20 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9356-1CR20 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9356-1CR20 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9356-1CR20 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9356-1CR20 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9356-1CR20 is a SENTRON RCD-operated circuit breaker (RCBO) combining overcurrent and residual current protection in a single 2-module-width package.

The 20 A rating is at 30 °C ambient; at 40 °C it derates to 18.8 A, at 45 °C to 18.2 A, at 50 °C to 17.4 A, and at 55 °C to 16.2 A. If your distribution board runs warm — say, tightly packed with other breakers — size the circuit load against the derated figure, not the nominal 20 A.

DIN-rail footprint and integration

Depth is 77 mm, height 90 mm, installation depth 70 mm. Mounting position any, supply feed from top or bottom. IP20 with conductors connected — meaning it's protected against finger contact only when wired inside a closed distribution board. Pollution degree 2, overvoltage category III, suitable for fixed installations downstream of the main panel.

Frequently asked questions

What is the closest functional second-source to 5SU9356-1CR20?

The 5SY5250-7 is a different class — it's an MCB without RCD protection. The 5SU9356-1CR20 is an RCBO combining overcurrent and residual current protection; there is no direct second-source that drops into the same panel without rewiring. For a functional equivalent, look for another 1P+N RCBO with 20 A Type C and 30 mA AC-type trip, 6 kA breaking capacity, 2 MW width.

Will 5SU9356-1CR20 drop into a panel specified around 5SY5250-7?

No — the 5SY5250-7 is an MCB only; the 5SU9356-1CR20 is an RCBO with a neutral connection and larger depth. The panel would need rewiring to accommodate the RCD function and neutral terminal.

What compliance documentation does Siemens provide for 5SU9356-1CR20?

The part carries EN 60898 certification for the MCB function and IEC/EN 61008 for the RCD function. It is halogen-free and silicon-free. Specific RoHS, REACH, and UL documentation should be requested at quote time.

Where can I buy 5SU9356-1CR20?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.