Siemens 5SU9356-1CS10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-1CS10 SENTRON RCD Circuit Breaker, 10 A, C-C

MPN5SU9356-1CS10

Siemens SENTRON 5SU9356-1CS10, RCD-operated circuit breaker, 1P+N, 10 A rated, C tripping characteristic, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 50 Hz, 2 width units (36 mm).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9356-1CS10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9356-1CS10 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9356-1CS10 — Mechanical
ParameterValue
Mounting positionany
Maximum1.5 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9356-1CS10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9356-1CS10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU9356-1CS10 is an RCD-operated circuit breaker — an RCBO — combining overcurrent protection and residual current detection in a single 1P+N package. It is rated 10 A at AC with a C tripping characteristic, meaning it handles moderate inrush from motor or lighting loads without nuisance tripping, while still clearing short circuits up to 6 kA per EN 60898 and 10 kA per IEC 60947-2.

Current derating and ambient limits

Above that, derate linearly: 9.4 A at 40 °C, 9.1 A at 45 °C, 8.7 A at 50 °C, and 8.1 A at 55 °C. The operating ambient range is -25 to +45 °C, so at the upper end you are already at 9.1 A continuous — factor that into panel loading if the enclosure runs warm. Storage range is -40 to +75 °C, which is wider than the operating range; that limit governs handling and shelf life, not running conditions.

The 5SU9356-1CS10 occupies 2 width units (36 mm) on a DIN rail, with an installation depth of 70 mm and overall depth of 77 mm. It accepts solid or stranded conductors from 0.75 mm² up to 35 mm² — that covers everything from a 1.5 mm² lighting circuit to a 10 mm² feeder.

Frequently asked questions

Is 5SU9356-1CS10 available via RFQ confirmation and what is the lead time?

We source this part to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count is held on this listing.

When sourcing 5SU9356-1CS10, what is the closest functional second-source — 5SL6563-7BB?

The 5SL6563-7BB is a different class of device — a miniature circuit breaker (MCB) without residual current protection. The 5SU9356-1CS10 is an RCBO (RCD + MCB combined). They are not drop-in substitutes; the 5SL series lacks the RCD function entirely.

What is 5SU9356-1CS10's listed depth?

The overall depth is 77 mm; the installation depth (behind the panel face) is 70 mm.

What wire sizes does 5SU9356-1CS10 accept?

It accepts solid or stranded conductors from 0.75 mm² up to 35 mm².

Will 5SU9356-1CS10 drop into a panel specified around 5SL6563-7BB without rewiring?

No — the 5SL6563-7BB is a plain MCB with no residual current module. The 5SU9356-1CS10 is an RCBO that requires the neutral connection for the RCD electronics. The physical footprint (2 width units, 36 mm) is the same, but the wiring differs.

What compliance documentation does Siemens provide for 5SU9356-1CS10?

As a current-production SENTRON device, it carries CE, UKCA, and EAC markings, and RoHS/REACH declarations are available on request. The part is designed to EN 60898 and IEC 60947-2.