Skip to main content
Siemens 5SU9356-1KN06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-1KN06 SENTRON RCBO, 6A C-curve, 10kA IEC

MPN5SU9356-1KN06
Active

Siemens SENTRON 5SU9356-1KN06, RCD-operated circuit breaker (RCBO), 6 A rated, C tripping characteristic, 1P+N, 2 poles, 10 kA breaking capacity per IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9356-1KN06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9356-1KN06 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9356-1KN06 — Mechanical
ParameterValue
Mounting positionany
Maximum1.5 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9356-1KN06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9356-1KN06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SU9356-1KN06 is a 1P+N RCD-operated circuit breaker (RCBO) combining overcurrent and residual current protection in a single 36 mm wide unit.

Current derating and ambient limits

Full rated current of 6 A holds at 30 °C ambient. Above that, derate: 5.64 A at 40 °C, 5.46 A at 45 °C, 5.22 A at 50 °C, and 4.86 A at 55 °C.

Supply can enter from top or bottom; mounting position is unrestricted. IP20 rated once installed in a distribution board with conductors connected.

Current production lifecycle stage — no end-of-life notice.

Frequently asked questions

What conductor sizes does 5SU9356-1KN06 accept?

Solid or stranded conductors from 0.75 mm² up to 35 mm². The terminal range covers typical branch-circuit wiring up to the sub-feed size.

MPN