Siemens 5SU9356-7KP06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-7KP06 SENTRON RCBO, 6A Type C, 30mA Type A,

MPN5SU9356-7KP06
Active

Siemens SENTRON 5SU9 series, RCD-operated circuit breaker (RCBO), 6 A rated, Type C tripping characteristic, 30 mA Type A residual current, 1P+N, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 36 mm wide.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU9356-7KP06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU9356-7KP06 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SU9356-7KP06 — Mechanical
ParameterValue
Mounting positionany
Maximum1.5 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU9356-7KP06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU9356-7KP06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

RCD-operated circuit breaker, 6 A Type C, 30 mA Type A

The Siemens 5SU9356-7KP06 is a SENTRON RCBO combining overcurrent protection and residual current detection in a single 36 mm wide module. Rated 6 A with a Type C tripping characteristic, it handles inrush from motor starters and lighting ballasts without nuisance trips. The Type A residual current element detects pulsating DC fault currents up to 30 mA, covering electronics and variable-speed drives. Breaking capacity is 6 kA per EN 60898 and 10 kA per IEC 60947-2, so it clears line-to-neutral faults on a standard 230/400 V distribution board without upstream reinforcement.

Mounting and conductor range

Two width units (36 mm) snap onto a DIN rail. Accepts solid or stranded copper from 0.75 to 35 mm², which covers most final subcircuit feeds up to 6 A. Installation depth is 70 mm; the overall depth including terminals is 77 mm — check gland-plate clearance if the enclosure is shallow. Mounting position is any, so it fits vertical or horizontal busbar arrangements.

Thermal derating and ambient limits

Rated 6 A at 30 °C ambient. Derate to 5.64 A at 40 °C, 5.46 A at 45 °C, 5.22 A at 50 °C, and 4.86 A at 55 °C. The maximum ambient for operation is 45 °C; storage range is -40 to +75 °C. If the panel runs hot (e.g., enclosed drives or transformers nearby), size the upstream protection for the derated current, not the 30 °C figure.

Frequently asked questions

What conductor sizes does the 5SU9356-7KP06 accept?

Solid or stranded copper from 0.75 to 35 mm².

What is the depth of the 5SU9356-7KP06?

Overall depth is 77 mm; installation depth is 70 mm.