Siemens 5SU9356-7KP10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-7KP10 SENTRON RCBO, 10 A, Type A, 6 kA

MPN5SU9356-7KP10
Active

Siemens SENTRON 5SU9 series, RCD-operated circuit breaker (RCBO), 1P+N, 10 A rated, Type A fault current, tripping characteristic C, 6 kA per EN 60898, 2 width units.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU9356-7KP10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU9356-7KP10 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SU9356-7KP10 — Mechanical
ParameterValue
Mounting positionany
Maximum1.5 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU9356-7KP10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU9356-7KP10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9356-7KP10 is a SENTRON RCD-operated circuit breaker — an RCBO combining overcurrent protection and residual current detection in a single 2-module (36 mm wide) package. Rated 10 A with a C tripping curve and Type A fault current sensitivity, it handles mixed loads with pulsed DC fault components common on single-phase electronics and small drives.

Breaking capacity and selectivity

Breaking capacity is 6 kA per EN 60898 and 10 kA per IEC 60947-2. The higher IEC figure gives headroom for industrial panel coordination where the upstream device is a molded-case breaker or fused switch; the EN figure governs domestic and light commercial distribution boards. Energy limiting class 3 means it lets through minimal let-through energy during a fault, which helps downstream selectivity.

Thermal derating and ambient limits

Rated 10 A at 30 °C ambient, the continuous current derates to 9.4 A at 40 °C, 9.1 A at 45 °C, 8.7 A at 50 °C, and 8.1 A at 55 °C. Operating ambient range is -25 to +45 °C; storage range is -40 to +75 °C. In a sealed enclosure or near heat-generating gear, the 45 °C limit is the governing constraint — above that, the derating curve applies and the 45 °C max ambient must not be exceeded.

Panel fit and wiring

Width 36 mm (2 width units), depth 77 mm, installation depth 70 mm. Mounts on DIN rail in any position. Conductor cross-section range 0.75 to 35 mm² for both solid and stranded — covers everything from 1.5 mm² lighting circuits up to 10 mm² feeder tails. Supply can enter from top or bottom. Touch protection is integrated on the busbar side.

Frequently asked questions

Where can I buy 5SU9356-7KP10 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current pricing and availability.

What is the difference between 5SU9356-7KP10 and 5SL6563-7BB?

The 5SL6563-7BB is a standard MCB without residual current protection. The 5SU9356-7KP10 is an RCBO combining overcurrent and RCD (Type A) functions in one unit. They are not direct drop-in replacements; the RCBO requires a neutral connection and occupies the same 2-module width but serves a different protection role.

What is 5SU9356-7KP10's listed depth?

The overall depth is 77 mm, with an installation depth of 70 mm behind the panel surface.

What conductor sizes does 5SU9356-7KP10 accept?

Both solid and stranded conductors from 0.75 mm² up to 35 mm².

What compliance documentation does this brand provide for 5SU9356-7KP10?

The part is designed to EN 60898 and IEC 60947-2, carries overvoltage category III rating, and is halogen-free and silicon-free. Specific RoHS/REACH declarations are typically available from the manufacturer upon request.