Siemens 5SU9356-7KP40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9356-7KP40 SENTRON RCBO, 40 A, 30 mA, Type A, 6 k

MPN5SU9356-7KP40
Active

Siemens SENTRON 5SU9356-7KP40, RCBO, 1P+N, 40 A, 30 mA, Type A, 6 kA per EN 60898, 2 MW, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU9356-7KP40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU9356-7KP40 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous

Mechanical

5SU9356-7KP40 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU9356-7KP40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU9356-7KP40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Key ratings and what they mean for your panel

The 5SU9356-7KP40: Rated 40 A at 30 °C, but the current must be derated as ambient temperature rises: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, and 32.4 A at 55 °C. For a panel running at 50 °C, you effectively have a 34.8 A device — plan your load accordingly. The breaking capacity is 6 kA per EN 60898 (the standard for MCBs/RCBOs in household and similar installations) and 10 kA per IEC 60947-2 (the industrial standard for low-voltage switchgear), so it handles fault currents up to 10 kA in an industrial panel. The C-curve trips at 5–10× In, suitable for motor and lighting loads with moderate inrush.

Mounting and integration

Snaps onto a DIN rail (2 MW width, 36 mm), accepts supply from either top or bottom, and can be mounted in any position. Installation depth is 70 mm; overall depth is 77 mm. Rated IP20 once installed in a distribution board with conductors connected — it is not a stand-alone outdoor device. Pollution degree 2 and overvoltage category III suit it for fixed installations in dry enclosures.

Frequently asked questions

What is the breaking capacity of 5SU9356-7KP40?

6 kA per EN 60898 and 10 kA per IEC 60947-2, so it covers both residential and industrial fault-level requirements.

How do I get pricing and availability for 5SU9356-7KP40?

Submit an RFQ — the part is sourced to order through independent distribution, and current pricing and availability are confirmed at quote time.

What is the temperature derating for 5SU9356-7KP40?

Rated 40 A at 30 °C, derated to 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, and 32.4 A at 55 °C.