5SU9404-0KK40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9404-0KK40 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9404-0KK40 — Mechanical
ParameterValue
Mounting positionany
Maximum0.75 W
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm
5SU9404-0KK40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9404-0KK40 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU9404-0KK40 is a SENTRON RCD-operated circuit breaker — an RCBO that combines overcurrent protection and residual current detection in one 18 mm-wide unit.

At 40 °C it derates to 37.6 A; at 45 °C to 36.4 A; at 50 °C to 34.8 A; at 55 °C to 32.4 A. Overvoltage category III means it's rated for fixed-installation distribution boards, not plug-in portable gear. It's a 1P+N design — one protected pole plus a switched neutral. The neutral pole is not overcurrent-protected; it just breaks and makes with the phase. For pulsating DC or smooth DC faults you'd need a type A or B RCD module. The instantaneous design means no intentional time delay — it trips within the standard RCD response window. Wire range accepts 0.75 to 35 mm² both solid and stranded. That covers everything from 1.5 mm² lighting circuits up to 10 mm² feeder tails. Installation depth is 70 mm; the overall depth is 77 mm. At 18 mm wide (one width unit), it fits standard DIN-rail enclosures with standard busbar spacing. Touch protection is built in, so live terminals are shielded when the breaker is in place.

Panel integration

The 18 mm width (one modular unit) means it takes up one slot in a distribution board. Supply can come from either top or bottom — no mandatory orientation.

Frequently asked questions

Where can I buy the 5SU9404-0KK40 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the 5SU9404-0KK40?

10 kA rated value per both EN 60898 and IEC 60947-2. That's the maximum short-circuit current it can safely interrupt.

What wire sizes does the 5SU9404-0KK40 accept?

Solid and stranded conductors from 0.75 mm² up to 35 mm². That covers most final subcircuit sizes in a distribution board.

What compliance documentation is available for this part?

The part carries approvals per EN 60898 and IEC 60947-2. It is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations are available on request at quote time.