It carries a 16 A rated current at 230/240 V AC with a C tripping characteristic and a 10 kA breaking capacity per EN 60898 and IEC 60947-2.
Derating and mounting
Rated 16 A at 30 °C ambient; derate to 15.04 A at 40 °C, 14.56 A at 45 °C, 13.92 A at 50 °C, and 12.96 A at 55 °C. Installation depth is 70 mm plus the 77 mm overall depth — check gland-plate clearance if the enclosure is shallow. Width is 18 mm (1 width unit), matching the standard modular grid; adjacent RCBOs or MCBs pack without wasted space.
Energy limiting class 3. Touch protection is provided. The product is halogen-free and silicon-free. Supply cord position can be top or bottom — no forced orientation. The design is instantaneous (no intentional time delay on the residual current element).