Siemens 5SU9404-1KK40 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9404-1KK40 SENTRON RCBO, 40A C-Curve, 10kA, 1P+N

MPN5SU9404-1KK40

Siemens SENTRON 5SU9 RCBO, RCD-operated circuit breaker, 40 A, C characteristic, 10 kA breaking capacity, 1P+N, 18 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU9404-1KK40 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9404-1KK40 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9404-1KK40 — Mechanical
ParameterValue
Mounting positionany
Maximum0.75 W
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm
5SU9404-1KK40 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9404-1KK40 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9404-1KK40 is a SENTRON 5SU9-series RCBO — an RCD-operated circuit breaker combining overcurrent and residual current protection in a single 18 mm module. Rated 40 A with a C tripping characteristic and 10 kA breaking capacity per EN 60898 and IEC 60947-2, it protects final circuits against overload, short-circuit, and AC earth faults in a 1P+N configuration.

Current derating and ambient limits

Above that, derate linearly: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C. For a panel running warm — say 45 °C internal ambient — the usable continuous current drops to 36.4 A, so size the upstream protection accordingly.

Snaps onto DIN rail, any mounting position. 18 mm wide (1 width unit), 77 mm deep, 125 mm tall; installation depth is 70 mm. IP20 with the distribution board installed and conductors connected.

Listed as current production — no obsolescence notice on record.

Frequently asked questions

Will 5SU9404-1KK40 drop into a panel specified around 5SU9304-1KK32?

Both are 18 mm wide SENTRON RCBOs on the same DIN-rail footprint, so mechanical fit is the same. The 5SU9404-1KK40 is a 40 A C-curve; the 5SU9304-1KK32 is a different rating/characteristic. Verify the circuit's load and fault-current requirements before substituting.

MPN
5SU9404-1KK40