Skip to main content
Siemens 5SU9604-1KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU9604-1KK06 SENTRON RCBO, 6 A, 10 kA, Type A, 30 m

MPN5SU9604-1KK06
Active

Siemens SENTRON 5SU9604-1KK06, RCBO, 1P+N, 6 A, C-curve, 10 kA, Type A, 30 mA, 1 MW.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU9604-1KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9604-1KK06 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9604-1KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height125 mm
Depth77 mm
Installation depth70 mm
5SU9604-1KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9604-1KK06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens 5SU9604-1KK06 is a SENTRON RCBO — a combined RCD and MCB in a single 1-module-wide (18 mm) package. The 1P+N design switches the line pole and monitors the neutral; the neutral is not switched.

The 10 kA breaking capacity (EN 60898 and IEC 60947-2) means this RCBO can safely interrupt a fault current up to 10,000 A — sufficient for most domestic and light commercial installations where the prospective short-circuit current at the board is under that threshold. The Type A residual current detection catches pulsating DC fault currents (e.g., from rectifiers or switched-mode supplies) that a Type AC device would miss. The 30 mA sensitivity provides personal protection against direct contact. Temperature derating is built in: at 40 °C the continuous rating drops to 5.64 A, at 50 °C to 5.22 A. If the board runs warm, size the circuit load accordingly. The device is rated for overvoltage category III (distribution level) and pollution degree 2, which covers typical indoor panel environments.

At 18 mm (1 MW) wide, it occupies a single module slot — critical when retrofitting into a crowded board. IP20 protection applies once the distribution board is installed and conductors are connected.

Frequently asked questions

What is the breaking capacity of 5SU9604-1KK06?

10 kA per both EN 60898 and IEC 60947-2, which covers most residential and light commercial distribution boards.

What is the difference between this RCBO and a standard MCB?

This unit combines overcurrent protection (MCB function) with residual current protection (RCD function) in one module. A standard MCB only protects against overload and short circuit; the 5SU9604-1KK06 also detects earth leakage at 30 mA (Type A), providing personal shock protection.

Where can I buy 5SU9604-1KK06 and how is it quoted?

It is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — no stock or price figures are published here.

MPN
5SU9604-1KK06