5SV1313-7KK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1313-7KK10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1313-7KK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1313-7KK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1313-7KK10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SV1313-7KK10 is a combined residual current circuit breaker with overcurrent protection (RCBO) — one module wide, 1P+N construction, rated 10 A at 30 °C with a 30 mA residual trip threshold. The C-curve characteristic means it holds 5–10× In for short overloads, then trips magnetically for fast fault clearing, which suits motor and lighting circuits with moderate inrush. The Type A RCD detects sinusoidal AC and pulsating DC residual currents, covering most modern electronics and single-phase drives.

The 10 A rating holds only at 30 °C ambient. At 40 °C it derates to 9.4 A, at 50 °C to 8.8 A, and at 60 °C to 8.1 A. If your distribution board runs warm — say 55 °C inside the enclosure — the continuous load should not exceed 8.4 A per pole. This is the figure that governs real-world circuit sizing, not the 30 °C label.

Depth is 77 mm, installation depth 70 mm. Mounting position is unrestricted, so it fits vertical or horizontal busbar arrangements. IP20 with the distribution board installed and conductors connected; the enclosure provides the environmental seal.

Frequently asked questions

Where can I buy 5SV1313-7KK10?

The part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

What is the residual current rating and type?

The 5SV1313-7KK10 trips at 30 mA residual current and is Type A, meaning it responds to sinusoidal AC and pulsating DC fault currents — the standard choice for circuits with rectifiers, switched-mode power supplies, or single-phase drives.

What compliance documentation is available for 5SV1313-7KK10?

The part carries EN 60898 certification for the 4.5 kA breaking capacity, is halogen-free and silicon-free, and is designed to Overvoltage Category III with Pollution Degree 2. Standard Siemens SENTRON documentation includes the declaration of conformity covering the applicable IEC/EN standards.

Will 5SV1313-7KK10 drop into a panel specified around 5SY4110-7CV?

Both are 1-module-wide Siemens RCBOs on the same DIN-rail footprint, so mechanical fit is identical. The 5SV1313-7KK10 is a Type A RCD with a C-curve MCB, while the 5SY4110-7CV is a different variant — verify the residual current type and tripping characteristic match your circuit design before substituting.

MPN
5SV1313-7KK10