Skip to main content
Siemens 5SV1313-7KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1313-7KK13 SENTRON RCBO, 13 A, Type A, 2-Pole, 4.

MPN5SV1313-7KK13
Active

Siemens SENTRON RCBO, 5SV1313-7KK13, 2-pole, 13 A rated, Type A residual current, C tripping characteristic, 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 1 MW wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1313-7KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1313-7KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1313-7KK13 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1313-7KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1313-7KK13 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Integrator's note — 5SV1313-7KK13

It breaks fault currents up to 4.5 kA per EN 60898 or 5 kA per IEC 60947-2, which covers most residential and light commercial panelboard applications. The 1-module-width (18 mm) footprint saves rail space in crowded enclosures — two of these fit in the same width as a standard 2-pole MCB. Mounting position is unrestricted, and supply can enter from either top or bottom, which simplifies busbar routing in a pre-wired board.

Temperature derating — what the numbers mean

At 40 °C it derates to 12.35 A, at 50 °C to 11.57 A, and at 70 °C to 10.01 A. If the panel runs warm — say 50 °C inside a sealed enclosure — the continuous load should not exceed 11.57 A per pole. This derating curve is published per IEC 60898 and is the same for all C-curve RCBOs in this series; it is not a safety margin but a thermal limit of the bimetal trip element.

Panel integration checklist

Depth 77 mm, height 90 mm — verify enclosure depth clearance (70 mm installation depth plus wiring space). Halogen-free and silicon-free construction meets low-smoke, zero-halogen material requirements for public-access buildings. Touch protection is integral on the line-side terminals.

Frequently asked questions

Where can I buy 5SV1313-7KK13 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, no stock figures listed here.

What is the closest functional second-source to 5SV1313-7KK13?

The 5SY6013-7 is a 1-pole MCB, not an RCBO — it lacks the residual current protection. For a 2-pole RCBO with Type A and C-curve, the 5SV1313-7KK13 is the correct SENTRON order code; no direct drop-in second-source exists without rewiring the residual current function.

Will 5SV1313-7KK13 drop into a panel specified around 5SY6013-7 without rewiring?

No. The 5SY6013-7 is a 1-pole MCB with no neutral switching or residual current detection. The 5SV1313-7KK13 is a 2-pole RCBO requiring both line and neutral connections plus a test circuit. The panel would need rewiring to accommodate the additional pole and the RCBO function.

What compliance documentation does Siemens provide for 5SV1313-7KK13?

The part carries IEC 60898 and IEC 60947-2 ratings, overvoltage category III, pollution degree 2, and is halogen-free and silicon-free. Standard Siemens declarations of conformity (CE, UKCA) and material compliance (RoHS, REACH) are available on request.