Siemens 5SV1313-7KK16 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV1313-7KK16 RCBO, 16 A, 30 mA, Type C, 1P+

MPN5SV1313-7KK16
Active

Siemens SENTRON RCBO, 1P+N, 16 A (30 °C), 30 mA, Type C, 4.5 kA (EN 60898), 5 kA (IEC 60947-2), 50 Hz, IP20, halogen-free, silicon-free.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1313-7KK16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1313-7KK16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1313-7KK16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1313-7KK16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1313-7KK16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

It protects a single-phase final circuit against overload, short-circuit, and earth leakage in one 18 mm-wide module. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2, sufficient for most domestic and commercial distribution boards where the prospective fault current stays under those thresholds.

The 16 A rating applies at 30 °C ambient. In a warm panel — say 45 °C — the continuous current drops to 14.72 A; at 55 °C it is 13.76 A; at 70 °C it is 12.32 A. If the circuit is loaded near 16 A and the enclosure runs hot, the RCBO will trip on thermal overload at a lower current than the nameplate suggests. That is the derating curve to check against the actual load and panel temperature.

Width is one modular unit (18 mm) — snaps onto standard DIN rail. Depth is 77 mm (installation depth 70 mm).

Frequently asked questions

Will 5SV1313-7KK16 drop into a panel specified around 5SU9354-7KK16 without rewiring?

Both are 1-module-wide (18 mm) DIN-rail RCBOs from the SENTRON family, so the mechanical fit is the same. However, verify the rated current, trip curve, and residual sensitivity match the circuit design before swapping.