Skip to main content
Siemens 5SV1316-0KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1316-0KK13 SENTRON RCBO, 13A, Type B, 6kA, 1P+N

MPN5SV1316-0KK13
Active

Siemens SENTRON 5SV1 series RCBO, 13 A rated current, tripping characteristic B, 6 kA breaking capacity per EN 60898, 1P+N, 18 mm width, instantaneous design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1316-0KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1316-0KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1316-0KK13 — Mechanical
ParameterValue
Mounting positionany
Maximum2.6 W
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1316-0KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1316-0KK13 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Thermal derating and power dissipation

The 5SV1316-0KK13: The rated current of 13 A applies at 30 °C ambient. The unit derates linearly: 12.35 A at 40 °C, 11.96 A at 45 °C, 11.57 A at 50 °C, 11.18 A at 55 °C, 10.79 A at 60 °C, 10.4 A at 65 °C, and 10.01 A at 70 °C. Maximum power dissipation is 2.6 W. Panel builders should account for this heat load when calculating enclosure thermal rise, especially in densely populated DIN-rail assemblies.

Dimensions and installation

Installation depth behind the panel is 70 mm. Supply connection can be from either top or bottom. Conductor cross-section range is 0.75 to 16 mm² for both solid and stranded wire.

The device is halogen-free and silicon-free. Overvoltage category is III. Energy limiting class is 3. The function code per DIN EN 61346-2 and DIN EN 81346-2 is F. The design series is 5SV1. The minimum test voltage for testing equipment is 195 V.

Frequently asked questions

Where can I buy 5SV1316-0KK13 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SV1316-0KK13's listed depth?

The listed depth is 77 mm, with an installation depth of 70 mm behind the panel.

What conductor cross-section does 5SV1316-0KK13 accept?

It accepts solid and stranded conductors from 0.75 to 16 mm².

What compliance documentation is available for 5SV1316-0KK13?

The device is halogen-free and silicon-free. It carries an overvoltage category III rating and is designed per EN 60898 with a 6 kA breaking capacity. The function code per DIN EN 61346-2 and DIN EN 81346-2 is F.

MPN
5SV1316-0KK13