Skip to main content
Siemens 5SV1316-1KK04 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV1316-1KK04 RCBO, 1P+N, 4 A, C-curve, 30 m

MPN5SV1316-1KK04
Active

Siemens SENTRON RCBO, 1P+N, 4 A rated, C characteristic, 30 mA residual current, 6 kA breaking capacity per EN 60898, 50 Hz, instantaneous design, 1 MW wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1316-1KK04 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1316-1KK04 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1316-1KK04 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1316-1KK04 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1316-1KK04 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SV1316-1KK04 is a 1P+N RCBO combining overcurrent protection and residual current detection in a single 18 mm-wide module. This is a current-production part in the SENTRON portfolio.

Rated 4 A at 30 °C ambient, the 5SV1316-1KK04 derates to 3.8 A at 40 °C, 3.6 A at 50 °C, and 3.2 A at 70 °C. In a warm panel — say 50 °C — you lose 0.4 A of headroom vs the 30 °C rating. Supply frequency is 50 Hz only — not 50/60 Hz dual-rated. Operating temperature range -40 to 75 °C.

Mounting position any.

Frequently asked questions

What is the breaking capacity of 5SV1316-1KK04?

6 kA rated breaking capacity per EN 60898, which covers the majority of residential and light commercial panel fault levels.

Does 5SV1316-1KK04 work on 60 Hz systems?

No — the supply frequency is rated 50 Hz only. It is not dual-rated for 60 Hz operation.

Where can I buy 5SV1316-1KK04?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between 5SV1316-1KK04 and the 5SY series RCBOs?

The 5SY series (e.g. 5SY4104-7CV) are also 1P+N RCBOs but typically carry different breaking capacities and may have different temperature derating curves. The 5SV1316-1KK04 is a SENTRON device with a 6 kA breaking capacity per EN 60898 and a published derating table down to 3.2 A at 70 °C. The 5SY variants should be checked against your specific fault level and ambient requirements before substituting.

MPN
5SV1316-1KK04