Siemens 5SV1316-1KK10 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV1316-1KK10 RCBO, 10A C-curve, 1P+N, 6kA E

MPN5SV1316-1KK10
Active

Siemens SENTRON RCBO, 1P+N, C-curve 10 A (30 °C), 6 kA per EN 60898, 10 kA per IEC 60947-2, 1 MW width, IP20 with conductors, 50 Hz only.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1316-1KK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1316-1KK10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1316-1KK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1316-1KK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1316-1KK10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SV1316-1KK10 is a 1P+N RCBO (residual current circuit breaker with overcurrent protection) in a 1-modular-width (18 mm) housing, rated 10 A at 30 °C with a C-curve tripping characteristic. It combines earth-leakage and overcurrent protection in one DIN-rail device — common in final subcircuits where both fault types must be cleared without a separate RCCB and MCB stack. Rated breaking capacity is 6 kA per EN 60898 and 10 kA per IEC 60947-2 — the higher IEC figure applies when the device is used as a distribution board component with a backup fuse or upstream breaker, giving the panel designer SCCR headroom for industrial panels that need 10 kA at 230 V.

The 10 A rating holds at 30 °C ambient; above that the device must be derated linearly to 7.4 A at 70 °C. This matters when the RCBO sits in a crowded enclosure — the 1 MW width (18 mm) limits self-heating, but a row of loaded breakers can raise internal ambient well past 40 °C, where the rating drops to 9.4 A. Installation depth is 70 mm plus the 77 mm overall depth, which fits standard 80 mm deep enclosures. The IP20 rating applies only when the distribution board is installed with connected conductors; the front face is finger-safe, but the terminals are not protected against water ingress.

Frequently asked questions

What is the breaking capacity of 5SV1316-1KK10?

6 kA per EN 60898 and 10 kA per IEC 60947-2 at 230 V AC.

What is the thermal derating for 5SV1316-1KK10?

Rated 10 A at 30 °C, derated to 9.4 A at 40 °C, 8.8 A at 50 °C, 8.1 A at 60 °C, and 7.4 A at 70 °C.

Where can I buy 5SV1316-1KK10?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.