Skip to main content
Siemens 5SV1316-1KK16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1316-1KK16 SENTRON RCBO, 1P+N, 16 A, C-curve, 6 k

MPN5SV1316-1KK16
Active

Siemens SENTRON 5SV1316-1KK16 RCBO, 1P+N, 16 A rated at 30 °C, C-curve, 6 kA per EN 60898, 10 kA per IEC 60947-2, 1-module wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1316-1KK16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1316-1KK16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1316-1KK16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1316-1KK16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1316-1KK16 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

Siemens 5SV1316-1KK16 — SENTRON RCBO, 1P+N, 16 A, C-curve

The Siemens 5SV1316-1KK16 is a 1P+N residual current operated circuit breaker (RCBO) from the SENTRON family, combining overcurrent and earth-fault protection in a single 18 mm wide module. The breaking capacity is 6 kA per EN 60898 for domestic/commercial panels and 10 kA per IEC 60947-2 for industrial distribution boards — that 10 kA figure is the one to use when coordinating with an upstream MCCB in an industrial panel. This is a 2-pole device (1P+N) with protection on the live pole only — the neutral is switched but not monitored for overcurrent. It's designed for single-phase final circuits where you need both fault protection and overcurrent protection in one DIN-rail slot.

The 16 A rating holds at 30 °C ambient, but it derates linearly as panel temperature climbs: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, 13.76 A at 55 °C, 13.28 A at 60 °C, 12.8 A at 65 °C, and 12.32 A at 70 °C. If the panel runs hot, size up or leave a spare slot for airflow.

Rated insulation voltage is 253 V, surge voltage resistance is 4 kV, and the minimum test voltage is 195 V. Operating frequency is 50 Hz only — there's no 60 Hz rating in the spec, so verify compatibility if the site uses 60 Hz supply.

Height is 90 mm. The IP20 rating applies only when the distribution board is installed with connected conductors — it's not a standalone weatherproof device. Spring-cage terminals accept standard copper conductors; no special tools beyond a screwdriver for the clamping screws.

Frequently asked questions

Where can I buy 5SV1316-1KK16 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Contact us with your quantity and target delivery window; availability and current pricing are confirmed at quote time.

What is 5SV1316-1KK16's listed depth (77 mm) on this component line?

The overall depth is 77 mm, with an installation depth of 70 mm behind the DIN-rail mounting surface.

What is 5SV1316-1KK16's listed width (18 mm) on this component line?

Width is 18 mm, which is one modular unit (1 MW) on standard DIN-rail distribution boards.

What compliance documentation does this brand provide for 5SV1316-1KK16?

The part is halogen-free and silicon-free. It carries ratings per EN 60898 (6 kA) and IEC 60947-2 (10 kA), with overvoltage category III and pollution degree 2. Standard Siemens documentation applies; verify specific RoHS/REACH/UL declarations with the manufacturer or your Siemens channel partner.

MPN
5SV1316-1KK16