Siemens 5SV1316-6GV06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1316-6GV06 SENTRON RCBO, B-Curve, 6A, 30 mA, 1P+N

MPN5SV1316-6GV06
Active

Siemens SENTRON 5SV1316-6GV06 RCBO, B-curve, 6 A rated at 30 °C, 30 mA residual current, 1P+N, 6 kA breaking capacity (EN 60898), 35 kA (IEC 60947-2), 230 V AC, 50 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1316-6GV06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1316-6GV06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1316-6GV06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1316-6GV06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1316-6GV06 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

It protects a 1P+N circuit against overload, short-circuit, and earth leakage in one device, saving a DIN-rail slot versus separate MCB + RCCB. The 30 mA residual-current element provides additional protection against electric shock.

Temperature derating — the real-world rating

The 6 A nameplate rating holds only at 30 °C ambient inside the panel. At 40 °C it's 5.64 A; at 50 °C, 5.28 A; at 60 °C, 4.86 A; at 70 °C, 4.44 A. If this RCBO lives in a crowded enclosure near transformers or drives, size the load against the derated figure, not the 30 °C number — a 5 A continuous load at 55 °C is already at the limit.

Snaps onto standard DIN rail, occupies one 18 mm modular width. Supply can come from top or bottom. The IP20 rating applies only after the distribution board is installed with conductors connected — it's not a standalone outdoor device. Depth is 77 mm, installation depth 70 mm, so it fits flush in a standard 90 mm deep enclosure. Mounting position is any, which helps when laying out a tight panel — vertical or horizontal orientation doesn't affect the trip performance.

Frequently asked questions

How do I get current pricing and availability for 5SV1316-6GV06?

Submit an RFQ through the storefront. Pricing and stock levels are confirmed at quote time — we source through independent distribution channels and quote to order.

What is 5SV1316-6GV06's listed depth on this component line?

77 mm total depth, with a 70 mm installation depth behind the panel face. The 18 mm width (1 modular unit) fits standard DIN-rail spacing.

Will 5SV1316-6GV06 drop into a panel specified around 5SY6040-6 without rewiring?

The 5SY6040-6 is a Siemens MCB only (no residual-current element), while the 5SV1316-6GV06 is an RCBO with integrated 30 mA RCD. They share the same 1-module-wide DIN footprint, so the mechanical fit is the same, but the wiring differs — the RCBO needs the neutral conductor routed through the device for the residual-current sensing. You can't simply swap one for the other without checking the circuit topology.