Breaking capacity is dual-rated: 6 kA per EN 60898 for the MCB function, and 25 kA per IEC 60947-2 for the RCBO assembly — that 25 kA figure is the one that matters for industrial panel SCCR coordination.
Fit and derating in the panel
Depth is 77 mm, with 70 mm installation depth needed behind the panel face — enough to clear the busbar and wiring gutters. Temperature derating is published across the full operating range: it carries its full 10 A up to 30 °C, then steps down to 9.4 A at 40 °C, 8.8 A at 50 °C, and 7.4 A at 70 °C.
Halogen-free and silicon-free construction, so it's safe for clean environments and won't outgas corrosive compounds near sensitive contacts or electronics.