Product Overview and Key Ratings
The Siemens SENTRON 5SV1316-6KK10 is a residual current operated circuit breaker (RCBO) combining overcurrent and residual current protection in a single 1P+N module.
Temperature Derating and Installation Constraints
Rated current is temperature-dependent: 10 A at 30 °C, derating to 9.4 A at 40 °C, 9.1 A at 45 °C, 8.8 A at 50 °C, 8.4 A at 55 °C, 8.1 A at 60 °C, 7.7 A at 65 °C, and 7.4 A at 70 °C. For a panel running at 50 °C ambient, the effective continuous current is 8.8 A — plan the load accordingly to avoid nuisance tripping. Mounting position is any, and supply can enter from top or bottom. IP20 rating applies only when installed in a distribution board with connected conductors — not for open-panel use.