Skip to main content
Siemens 5SV1316-6KK10 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV1316-6KK10 RCBO, 10 A, 6 kA, Type B

MPN5SV1316-6KK10
Active

Siemens SENTRON RCBO, 1P+N, 10 A (30 °C), 6 kA (EN 60898), Type B, 1 MW, 18 mm wide.

$41.91 – $106.42Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1316-6KK10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1316-6KK10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1316-6KK10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1316-6KK10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1316-6KK10 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Product Overview and Key Ratings

The Siemens SENTRON 5SV1316-6KK10 is a residual current operated circuit breaker (RCBO) combining overcurrent and residual current protection in a single 1P+N module.

Temperature Derating and Installation Constraints

Rated current is temperature-dependent: 10 A at 30 °C, derating to 9.4 A at 40 °C, 9.1 A at 45 °C, 8.8 A at 50 °C, 8.4 A at 55 °C, 8.1 A at 60 °C, 7.7 A at 65 °C, and 7.4 A at 70 °C. For a panel running at 50 °C ambient, the effective continuous current is 8.8 A — plan the load accordingly to avoid nuisance tripping. Mounting position is any, and supply can enter from top or bottom. IP20 rating applies only when installed in a distribution board with connected conductors — not for open-panel use.

Frequently asked questions

What is the closest functional alternative if 5SV1316-6KK10 is unavailable?

The 5SL4363-7 is a different product class (MCB only, no residual current protection) and cannot substitute an RCBO without adding a separate RCD. For a direct RCBO replacement, stay within the SENTRON 5SV series with matching ratings.

What compliance documentation is available for this RCBO?

The part is halogen-free and silicon-free per the specification. It is designed to EN 60898 and IEC 60947-2, with breaking capacities of 6 kA and 25 kA respectively. Overvoltage category III and pollution degree 2 are documented.

MPN