Rated current and breaking capacity — what governs the BOM fit
The 5SV1316-6KK16: That dual rating means it covers residential and light commercial panels (EN 60898) and industrial distribution boards (IEC 60947-2) with a single device — no need to swap breakers when the installation standard changes. The Type B tripping characteristic trips instantaneously at 3–5× rated current, designed for resistive and inductive loads without high inrush — lighting circuits, heating elements, general socket outlets. The 1P+N design protects one phase and switches the neutral without monitoring it.
One modular unit wide (18 mm) with a 77 mm depth and 90 mm height — fits standard DIN-rail enclosures without oversizing the cabinet. Supply can enter from either top or bottom, which simplifies panel layout when busbars run on one side. IP20 protection applies once the distribution board is installed with connected conductors.