Siemens 5SV1316-7GV13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1316-7GV13 SENTRON RCBO, 2-pole 13A C-curve 6kA

MPN5SV1316-7GV13
Active

Siemens SENTRON 5SV1316-7GV13 RCBO, 2-pole 1P+N, 230 V AC, 13 A rated current, tripping characteristic C, 6 kA breaking capacity per EN 60898, Type A fault current, instantaneous design, halogen-free, silicon-free, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SV1316-7GV13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SV1316-7GV13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SV1316-7GV13 — Mechanical
ParameterValue
Mounting positionany
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SV1316-7GV13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SV1316-7GV13 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SV1316-7GV13 is a 2-pole RCBO (residual current circuit breaker with overcurrent protection) in a 1P+N configuration, rated for 230 V AC at 50 Hz. It carries a 13 A rated current at 30 °C with a C tripping curve and a 6 kA breaking capacity per EN 60898 — the standard for household and similar installations. The Type A fault current detection means it handles pulsating DC residual currents from single-phase rectifiers, common in modern electronics loads.

Thermal derating and panel fit

Rated current drops with ambient temperature: 12.35 A at 40 °C, 11.57 A at 50 °C, and 10.01 A at 70 °C. The 18 mm width (1 width unit) and 77 mm depth (70 mm installation depth) fit standard DIN-rail enclosures. Mounting position is unrestricted. Feed from top or bottom — no orientation constraint. IP20 with the distribution board installed and conductors connected.

Frequently asked questions

Where can I buy 5SV1316-7GV13 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the thermal derating for 5SV1316-7GV13?

Rated current is 13 A at 30 °C, derating to 12.35 A at 40 °C, 11.57 A at 50 °C, and 10.01 A at 70 °C.

What compliance documentation does this RCBO carry?

Rated per EN 60898 for breaking capacity, halogen-free and silicon-free. Overvoltage category III, pollution degree 2.

MPN