Rated 2 A at 30 °C ambient with a C tripping characteristic (magnetic release between 5× and 10× In), it handles resistive and moderate motor-start loads on 230 V AC, 50 Hz circuits. Thermal derating is published across the full ambient range: 1.9 A at 40 °C, 1.8 A at 50 °C, 1.7 A at 60 °C, and 1.6 A at 70 °C.
Installation depth is 70 mm plus the 77 mm overall depth — plan gland-plate clearance accordingly. Surge voltage withstand is 4 kV.