Skip to main content
Siemens 5SV1613-6KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1613-6KK06 SENTRON RCBO 2-pole Type A 6 A B-curve

MPN5SV1613-6KK06
Active

Siemens SENTRON RCBO, 2-pole (1P+N), Type A, 6 A, B-curve, 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 1 MW, 18 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1613-6KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1613-6KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1613-6KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1613-6KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1613-6KK06 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

RCBO for mixed resistive and motor loads

The Siemens 5SV1613-6KK06 is a SENTRON RCBO combining a Type A residual current device with a B-curve MCB in a single 1-module-width (18 mm) package. It protects against earth faults with DC-sensitive detection (Type A) and overcurrent/short-circuit with a 6 A B-curve thermal-magnetic trip. The 4.5 kA breaking capacity per EN 60898 and 5 kA per IEC 60947-2 cover most residential and light commercial panel fault levels.

Sizing and derating in the panel

At 30 °C the unit is rated a full 6 A. Above that, derate linearly: 5.64 A at 40 °C, 5.28 A at 50 °C, 4.86 A at 60 °C, and 4.44 A at 70 °C. In a crowded enclosure where ambient hits 50 °C, plan for 5.28 A continuous — not the 6 A label.

Mounting and wiring flexibility

Mounts in any position — no derating for orientation. The 2-pole (1P+N) design switches the line conductor only; the neutral is switched through the RCD. IP20 protection applies once the distribution board is installed and conductors are connected.

Frequently asked questions

Where can I buy the 5SV1613-6KK06 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the depth of the 5SV1613-6KK06?

The listed depth is 77 mm, with an installation depth of 70 mm.

What is the width of the 5SV1613-6KK06?

The width is 18 mm, which is 1 modular width unit.

Will the 5SV1613-6KK06 drop into a panel specified around the 5SL3116-6MB without rewiring?

Both are 1-module-width (18 mm) DIN-rail RCBOs, but the 5SL3116-6MB is a different series with its own wiring and accessory layout. Verify the terminal positions and neutral bar arrangement against the existing panel layout before assuming a drop-in fit.

MPN
5SV1613-6KK06