Skip to main content
Siemens 5SV1613-7KK02 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV1613-7KK02 RCBO, 2 A, C Curve, 300 mA, 1P

MPN5SV1613-7KK02
Active

Siemens SENTRON RCBO, 5SV1613-7KK02, 2 A rated, C characteristic, 300 mA residual current Type A, 1P+N, 4.5 kA breaking capacity, 1 MW wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1613-7KK02 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1613-7KK02 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1613-7KK02 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1613-7KK02 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1613-7KK02 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

It combines a C-curve miniature circuit breaker (MCB) for overcurrent protection with a 300 mA Type A residual current device (RCD) for earth fault protection, all in one device that snaps onto a DIN rail. The 300 mA residual current rating is a standard for general socket-outlet protection in commercial or residential final circuits, not the 30 mA required for personal shock protection. The device is rated for 50 Hz systems only, with a Type A residual current characteristic — it detects sinusoidal AC residual currents plus pulsating DC residual currents, covering most modern electronic loads like switched-mode power supplies and variable-speed drives that generate pulsating fault currents.

Installation depth is 70 mm — check your enclosure depth if using a shallow distribution board. Supply can enter from either top or bottom, so no need to flip the busbar arrangement. The IP20 rating applies when installed in a distribution board with connected conductors — it's not a standalone outdoor device.

Rated 2 A at 30 °C ambient, but derates linearly to 1.6 A at 70 °C.

Frequently asked questions

What is the breaking capacity of 5SV1613-7KK02?

Rated 4.5 kA according to EN 60898, which is the standard for miniature circuit breakers in household and similar installations.

What is the residual current rating and type?

300 mA, Type A — detects sinusoidal AC and pulsating DC residual currents, suitable for circuits with electronic loads.

Where can I buy 5SV1613-7KK02?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SV1613-7KK02 drop into a panel specified for 5SU9304-1KK32?

Both are 1 MW wide RCBOs from the SENTRON family, but the 5SU9304-1KK32 is a different variant — check the rated current, residual current, and characteristic before substituting. The 5SV1613-7KK02 is 2 A, C curve, 300 mA Type A; the 5SU9304-1KK32 may differ in these ratings.

MPN
5SV1613-7KK02