Siemens 5SV1613-7KK13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV1613-7KK13 SENTRON RCBO, 13 A, Type A, 4.5 kA

MPN5SV1613-7KK13
Active

Siemens SENTRON RCBO, 5SV1613-7KK13, 2-pole 1P+N, 13 A, Type A, C characteristic, 4.5 kA per EN 60898, 1 MW width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1613-7KK13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1613-7KK13 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1613-7KK13 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1613-7KK13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1613-7KK13 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

It protects against both overload/short-circuit and earth leakage in one device, saving a DIN-rail position compared to separate MCB + RCCB.

Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2. For higher fault levels, step up to the 5SY series. The 1P+N configuration switches the line conductor only; the neutral is switched internally but not protected. Temperature derating is published: 12.35 A at 40 °C, 11.57 A at 50 °C, 10.79 A at 60 °C.

Depth is 77 mm (70 mm installation depth), so it clears most shallow enclosures. IP20 with the distribution board installed and conductors connected; not rated for wet or dusty environments.

Listed as current production. Standard catalog item in the SENTRON RCBO family.

Frequently asked questions

What is the difference between 5SV1613-7KK13 and 5SL6016-7KL?

The 5SL6016-7KL is a standard MCB (no residual current protection), while the 5SV1613-7KK13 is an RCBO combining overcurrent and earth leakage protection in one module. They are not drop-in substitutes — the RCBO requires a neutral connection and adds Type A residual current detection.

MPN