Skip to main content
Siemens 5SV1616-7KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV1616-7KK06 RCBO, 6A C-curve, 300mA Type A

MPN5SV1616-7KK06
Active

Siemens SENTRON RCBO, 1P+N, 6 A rated, C characteristic, 300 mA residual current Type A, 6 kA per EN 60898, instantaneous design, 18 mm width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV1616-7KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV1616-7KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SV1616-7KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units1
Maximum75 °C
Minimum-40 °C
Width18 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SV1616-7KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV1616-7KK06 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

The Siemens SENTRON 5SV1616-7KK06 is a 1P+N RCBO (residual current circuit breaker with overcurrent protection) in an 18 mm single-module width, combining a C-curve thermal-magnetic overcurrent trip at 6 A with a 300 mA Type A residual current detection element. Type A residual current detection means it trips on sinusoidal AC fault currents and also on pulsating DC fault currents — the standard requirement for circuits with single-phase rectified loads like washing machines, LED drivers, and IT equipment.

Derating and ambient temperature

Rated 6 A at 30 °C ambient, the continuous current must be derated as panel temperature rises: 5.64 A at 40 °C, 5.46 A at 45 °C, 5.28 A at 50 °C, 5.04 A at 55 °C, 4.86 A at 60 °C, 4.62 A at 65 °C, and 4.44 A at 70 °C.

Mountable in any position, with supply feed from either top or bottom — no mandatory orientation, which simplifies layout in crowded enclosures.

Listed as current production.

Frequently asked questions

What is the depth of 5SV1616-7KK06?

The depth is 77 mm, with an installation depth of 70 mm behind the panel face.

What is the width of 5SV1616-7KK06?

The width is 18 mm, occupying 1 modular unit on a DIN rail.

Will 5SV1616-7KK06 drop into a panel specified around 5SY4106-7CV?

Both are 1-module-wide (18 mm) DIN-rail RCBOs, so the physical footprint is the same — but verify the rated current, trip characteristic, residual current type, and breaking capacity against the panel design before swapping, as those ratings differ between order codes.

MPN
5SV1616-7KK06