The Siemens 5SV1616-7KK13 is a SENTRON RCBO combining overcurrent and residual current protection in a 2-pole, 1-module-width (18 mm) package. The C characteristic means it trips at 5–10 times rated current for moderate inrush — typical for mixed resistive and inductive loads in final circuits.
The 13 A rating holds up to 30 °C ambient; above that it must be derated: 12.35 A at 40 °C, 11.57 A at 50 °C, 10.79 A at 60 °C, and 10.01 A at 70 °C. Mounting position is unrestricted, which simplifies panel layout.
Integration notes
Mounts on DIN rail, 1 MW wide (18 mm). Depth of 77 mm and installation depth of 70 mm fit standard distribution boards. IP20 with conductors connected — suitable for enclosed panel use only. Touch protection is built in.