Siemens 5SV3312-6BA — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3312-6BA SENTRON RCCB, 2-pole, 25 A, 30 mA, Type

MPN5SV3312-6BA

Siemens SENTRON 5SV3312-6BA, 2-pole RCCB, Type A, 25 A rated, 30 mA trip, 230 V AC, 10 kA SCCR, instantaneous, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3312-6BA — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV3312-6BA — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV3312-6BA — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3312-6BA — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV3312-6BA — Electrical
ParameterValue
Operational current / at AC / rated value25 A

Product details

The Siemens 5SV3312-6BA is a SENTRON residual current circuit breaker (RCCB) — a 2-pole, Type A device rated at 25 A with a 30 mA trip threshold, designed for 230 V AC systems. It carries a 10 kA short-circuit current rating (SCCR) per IEC 61008-1 and a 0.5 kA rated conditional short-circuit current per EN 60898. The instantaneous design means it trips without intentional delay on residual currents exceeding 30 mA, providing personnel protection against direct contact in final circuits.

The 30 mA trip threshold is the common personnel-protection level (IEC 60364-4-41), suitable for socket-outlet circuits, lighting, and general-purpose final subcircuits where the touch voltage must stay below 50 V. Rated current holds at 25 A from 40 °C through 60 °C ambient, then derates to 23.3 A at 65 °C and 17.62 A at 70 °C. In a warm panel (55 °C typical near a transformer or drive), the 25 A rating is still valid — no derating needed. Above 60 °C, the thermal curve governs; a 16 A load is safe at 70 °C, but a 20 A continuous load would risk nuisance tripping.

Mounting position is unrestricted, which simplifies layout in a crowded enclosure. The supply can enter from the top or bottom, so busbar routing is flexible. It is silicon-free, which matters for automotive or aerospace panels where silicone outgassing can contaminate contacts or optics.

Frequently asked questions

What is the 5SV3312-6BA used for?

It is a residual current circuit breaker (RCCB) for personnel protection in 230 V AC final circuits. The Type A, 30 mA trip characteristic covers socket outlets, lighting, and circuits with single-phase electronic loads where pulsating DC fault currents may occur.

What are the key ratings of the 5SV3312-6BA?

2-pole, 25 A rated current (holds to 60 °C ambient), 30 mA residual trip, Type A, 230 V AC, 10 kA SCCR per IEC 61008-1, instantaneous design. Occupies 2 MW (36 mm) on DIN rail.

Where can I buy the 5SV3312-6BA?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

Will the 5SV3312-6BA drop into a panel specified for 5SL6550-7BB?

Both are 2-pole, 36 mm wide DIN-rail RCCBs, so the physical footprint matches. However, the 5SL6550-7BB is a 50 A device with a different trip characteristic; verify the load current and selectivity coordination before swapping. The 5SV3312-6BA is a 25 A Type A unit — it is not a direct functional substitute for a 50 A RCCB.

MPN