Skip to main content
Siemens 5SV3322-4 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3322-4 SENTRON RCCB, 2-pole Type B, 25 A 30 mA

MPN5SV3322-4
Active

Siemens SENTRON RCCB, 2-pole, Type B, short-time delayed, In: 25 A, 30 mA, Un AC: 230 V, 10 kA SCCR, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV3322-4 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV3322-4 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SV3322-4 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3322-4 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV3322-4 is a 2-pole residual current operated circuit breaker (RCCB) from the SENTRON series, rated 25 A with 30 mA sensitivity, Type B, short-time delayed, for 230 V AC at 50/60 Hz. Type B detection means it catches AC sinusoidal residual currents, pulsating DC, and smooth DC up to the rated sensitivity — critical for drives, UPS systems, and PV inverters that can generate DC fault currents a standard Type A would miss. The short-time delayed design (SIGRES function) prevents nuisance tripping from transient surge currents or inrush from downstream equipment, making it suitable for feeder circuits where selectivity with downstream RCCBs is required.

Snaps onto DIN rail (REG) — standard 35 mm rail in any mounting position. Depth is 70 mm, matching the installation depth. IP20 with connected conductors in an installed distribution board — intended for enclosed panel use, not open washdown areas.

The series fuse maximum permissible is 100 A for backup protection. Power dissipation is 1.2 W per pole in hot operating state at rated current — low enough to avoid derating concerns in a densely packed DIN rail enclosure, but still worth summing across all poles for thermal budget. Ambient operating range -25 °C to +45 °C; storage down to -40 °C.

Silicon-free construction matters for automotive paint-shop or semiconductor fab environments where silicone outgassing can contaminate surfaces.

Frequently asked questions

What is the 5SV3322-4 used for?

It is a Type B RCCB for 2-pole 230 V AC circuits, rated 25 A with 30 mA sensitivity, short-time delayed. Use it where DC fault currents may occur (drives, UPS, solar) and where selectivity with downstream RCCBs is needed.

Will the 5SV3322-4 drop into a panel designed for a 5SL4363-7?

No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) with different width (54 mm / 3 MW) and function. The 5SV3322-4 is a 2-pole RCCB at 72 mm / 4 MW. They are not footprint- or function-interchangeable without rewiring.

Where can I buy the 5SV3322-4?

This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN