Skip to main content
Siemens 5SV3344-4KK60 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3344-4KK60 SENTRON RCCB, 40 A, 30 mA Type B, 4-po

MPN5SV3344-4KK60
Active

Siemens SENTRON RCCB, 5SV3344-4KK60, 4-pole, 40 A, 30 mA Type B, short-time delayed, 10 kA SCCR, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV3344-4KK60 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3344-4KK60 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SV3344-4KK60 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3344-4KK60 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

Type B means it detects smooth DC residual currents, AC sinusoidal currents, and pulsed DC — covering variable-speed drives, UPS systems, and PV inverters that a standard AC or A-type RCCB would miss. The short-time delayed design (0.8 kA surge current withstand per IEC 61008-1) prevents nuisance tripping from transient surge currents like lightning or switching spikes, so it belongs in circuits feeding electronic loads.

Supply voltage range is 70–440 V AC at 50/60 Hz, covering standard 230/400 V three-phase panels. The 3 kA surge current resistance and 60 000 A²·s I²t withstand give the integrator confidence against inrush from downstream capacitive loads. Mounts on DIN rail (REG) in any position — no orientation restrictions. Occupies 4 modular width units (72 mm wide, 70 mm deep, 90 mm high) with 60 mm grid spacing. Silicon-free construction suits coating-sensitive environments like automotive paint lines or electronics assembly.

Frequently asked questions

What is the 5SV3344-4KK60 used for?

It is a Type B RCCB for detecting all forms of residual current (AC, pulsed DC, and smooth DC) in circuits with variable-speed drives, UPS systems, or PV inverters. The 30 mA sensitivity provides personnel protection; the short-time delayed characteristic avoids nuisance trips from surge currents.

Where can I buy the 5SV3344-4KK60?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What are the key ratings of the 5SV3344-4KK60?

40 A rated current, 30 mA Type B residual trip, 4-pole, short-time delayed, 10 kA SCCR, 70–440 V AC supply range, 50/60 Hz, DIN rail mount, IP20, silicon-free.

MPN
5SV3344-4KK60