Skip to main content
Siemens 5SV3346-4 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3346-4 SENTRON RCCB, 4P, Type B, 63 A, 30 mA, 400

MPN5SV3346-4
Active

Siemens SENTRON RCCB, 4-pole, Type B, short-time delayed, In: 63 A, IΔn: 30 mA, Un AC: 400 V, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3346-4 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3346-4 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SV3346-4 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3346-4 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

Siemens 5SV3346-4 SENTRON RCCB — 4-pole Type B, 63 A, 30 mA

It is rated at 63 A with a 30 mA residual current sensitivity, operating on a 400 V AC supply at 50/60 Hz. This is the variant you spec into a panel where you need all-pole disconnection and protection against sinusoidal AC, pulsating DC, and smooth DC fault currents — Type B covers the full range, including variable-speed drive and UPS leakage. The 30 mA sensitivity provides personal protection against direct contact. The short-time delayed characteristic (SIGRES function) withstands brief inrush without nuisance tripping. Supply voltage range is 70 V to 440 V AC.

The 70 mm installation depth matches standard distribution board cutouts. The silicon-free construction is relevant for automotive or aerospace panel environments where silicone outgassing can contaminate contacts or optics.

Rated short-circuit current (IEC 61008-1) is 0.8 kA, with a maximum permissible series fuse short-circuit current of 100 A. The conditional short-circuit rating of 10 kA applies when backed by an upstream protective device — typical for a sub-distribution board fed from a main breaker. Overvoltage category III suits fixed installation downstream of the utility meter. This covers most indoor industrial and commercial environments; if the panel sits in an unconditioned space that sees below -25 °C, the storage minimum is fine but operation requires the warmer range.

Frequently asked questions

What is the depth of the 5SV3346-4?

The Siemens 5SV3346-4 has a depth of 70 mm, which is also the installation depth required in the distribution board.

MPN
5SV3346-4