Skip to main content
Siemens 5SV3346-4KK14 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3346-4KK14 SENTRON RCCB, 4P, 63A, 30mA, Type B+

MPN5SV3346-4KK14
Active

Siemens SENTRON RCCB, 4-pole, Type B+, short-time delayed, In: 63 A, 30 mA, Un AC: 400 V, 10 kA SCCR, DIN rail mount, 4 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3346-4KK14 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3346-4KK14 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SV3346-4KK14 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3346-4KK14 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SV3346-4KK14 is a 4-pole residual current operated circuit breaker (RCCB) with a Type B+ characteristic, rated 63 A and 30 mA sensitivity at 400 V AC. The Type B+ curve detects smooth DC fault currents plus AC and pulsed DC — critical for variable-speed drives, UPS systems, and PV inverters where standard AC-only RCCBs would be blind to a fault. The 30 mA trip threshold meets the IEC 61008-1 requirement for personal protection (additional protection against direct contact).

Short-time delayed design and selectivity

This RCCB is short-time delayed (S-type), meaning it withstands transient leakage currents without tripping — essential for selectivity in a distribution board where downstream RCCBs clear first. The short-circuit current rating is 10 kA, and per IEC 61008-1 the rated conditional short-circuit current is 0.8 kA. The maximum permissible series fuse short-circuit current is 100 A, which governs the upstream protection you pair it with.

Depth is 70 mm, height 90 mm. Mounting position is unrestricted. Silicon-free construction suits coating-sensitive environments like automotive paint lines.

Frequently asked questions

What is 5SV3346-4KK14 used for?

It is a 4-pole Type B+ RCCB for 400 V AC, 63 A, 30 mA residual current protection. The Type B+ characteristic handles smooth DC, AC, and pulsed DC faults, making it suitable for circuits with variable-speed drives, UPS systems, or PV inverters.

Where can I buy 5SV3346-4KK14?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN