Skip to main content
Siemens 5SV3416-6KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3416-6KL SENTRON RCCB, 2-pole, 63 A, 100 mA, Type

MPN5SV3416-6KL
Active

Siemens SENTRON 5SV3416-6KL, 2-pole RCCB, 63 A, 100 mA Type A, 10 kA, 50 Hz, DIN rail, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3416-6KL — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV3416-6KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV3416-6KL — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3416-6KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

RCCB for 50 Hz panels — 63 A, 100 mA Type A, 10 kA SCCR

The Siemens 5SV3416-6KL is a 2-pole SENTRON RCCB rated 63 A with a 100 mA Type A trip characteristic, designed for 50 Hz installations. Type A detection catches pulsating DC residual currents from single-phase rectified loads.

Snaps onto standard DIN rail (REG per) in any mounting position. Supply feeds top or bottom — no polarity constraint. IP20 rating applies only when the distribution board is installed with connected conductors; the body itself is not sealed against washdown. Silicon-free construction suits environments where outgassing must be avoided, such as sealed enclosures near sensitive optics or coating lines.

Rated 63 A continuously from 40 °C through 55 °C ambient. At 65 °C it derates to 56.96 A; at 70 °C to 48.2 A. Storage range is -40 to +75 °C, operating range -25 to +45 °C. The 1 kA surge current resistance and 110 000 A²s I²t withstand cover inrush from downstream loads without nuisance tripping.

Current production. No LTB or EOL notice.

Frequently asked questions

What is the closest functional second-source to 5SV3416-6KL?

The 5SU9354-7KK16 is a peer RCCB in the same SENTRON family. Verify your panel's rated current, trip sensitivity, and pole count against that order code before substituting — the 5SV3416-6KL is a 2-pole, 63 A, 100 mA Type A device at 50 Hz.

Will 5SV3416-6KL drop into a panel specified around 5SU9354-7KK16 without rewiring?

Both are DIN-rail RCCBs in the SENTRON family, but the 5SV3416-6KL is a 2-pole, 63 A, 100 mA Type A unit. Confirm the existing panel's rated current, pole count, and trip sensitivity match before direct swap — do not assume identical footprint or wiring without checking the nameplate.

MPN