Skip to main content
Siemens 5SV3612-6KK01 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3612-6KK01 SENTRON RCCB, 25 A, 300 mA, 2-Pole, Sh

MPN5SV3612-6KK01
Active

Siemens SENTRON RCCB, 25 A, 300 mA, Type A, short-time delayed, 2-pole, 10 kA SCCR, 230/400 V AC, 50/60 Hz, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV3612-6KK01 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV3612-6KK01 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SV3612-6KK01 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3612-6KK01 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

It is short-time delayed (short-term delayed per the design), meaning it tolerates brief surge currents up to 3 kA without nuisance tripping — useful on circuits with motor inrush or capacitor banks. The 10 kA short-circuit current rating (SCCR) at 230/400 V AC, 50/60 Hz means it safely interrupts fault currents up to that level without cascading upstream. Type A detection covers sinusoidal AC and pulsating DC residual currents, which is the standard requirement for most modern electronic loads like VFDs, switching power supplies, and LED drivers.

Snaps onto standard DIN rail (REG per the spec). Depth is 70 mm, height 90 mm. Mounting position is any orientation, so it fits vertical or horizontal busbar layouts.

Thermal performance and derating

The I²t let-through is 58,000 A²·s, with a peak let-through current of 5,200 A. Silicon-free construction, which matters for certain coating and potting processes in sensitive electronics environments.

Frequently asked questions

Where can I buy 5SV3612-6KK01 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number.

What is 5SV3612-6KK01's listed depth (70 mm) on this component line?

The listed depth is 70 mm. That is the installed depth on the DIN rail, not including any front projection for the handle or terminals.

What is 5SV3612-6KK01's listed width (36 mm) on this component line?

The width is 36 mm, which corresponds to 2 modular width units on a standard DIN-rail panel. This is a 2-pole device in a compact footprint.

What compliance documentation does this brand provide for 5SV3612-6KK01 (RoHS, REACH, UL, IEC)?

The part is designed per IEC 61008-1 (the RCCB standard) with a rated conditional short-circuit current of 0.5 kA under that standard. The SENTRON series typically carries CE marking for the European market. For specific RoHS/REACH declarations or UL listing, request the manufacturer's declaration at quote time.

MPN
5SV3612-6KK01