The 5SV3614-3: Mounts on DIN rail (REG) in any position, occupying 2 modular width units at 60 mm grid spacing. The 70 mm installation depth and 36 mm width match the standard SENTRON modular footprint — drops directly into a panel already laid out for 2-pole SENTRON MCBs or RCCBs without rewiring the busbar or gland plate. IP20 with distribution board installed — suitable for enclosed panel environments, not for wet washdown.
Type F design handles mixed-frequency residual currents from variable-speed drives and single-phase rectifiers — not just 50/60 Hz sine-wave faults. The short-time delayed characteristic avoids nuisance tripping from transient leakage that would trip a standard instantaneous RCCB. Rated for 230/400 V AC supply at 50/60 Hz. Silicon-free construction. Overvoltage category III. Mechanical service life of 10 000 operating cycles typical.
Lifecycle status is active — this is a current-production part from the SENTRON RCCB line.