Skip to main content
Siemens 5SV3642-8 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3642-8 SENTRON RCCB, 25 A, 300 mA, 4-pole, select

MPN5SV3642-8
Active

Siemens SENTRON selective RCCB, 4-pole type A, 25 A rated current, 300 mA residual, 400 V AC, 10 kA SCCR, 4 MW DIN rail.

$48.26Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV3642-8 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3642-8 — Identification
ParameterValue
Product designationRCCB
Product design / constructionSelective
5SV3642-8 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3642-8 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

Selective RCCB for feeder discrimination

The Siemens 5SV3642-8 is a 4-pole selective residual current circuit breaker (RCCB) from the SENTRON family, rated 25 A with a 300 mA residual operating current at 400 V AC. The selective design (time-delayed) means it coordinates with downstream instantaneous RCDs — in a fault, the downstream device trips first, keeping this unit closed so only the faulted branch drops, not the whole sub-distribution board. That makes it the right choice for a feeder or main switch position where you need discrimination from branch RCDs. Type A detection covers AC sinusoidal and pulsating DC residual currents — the common profile for single-phase rectified loads like switching power supplies, LED drivers, and variable-speed drives. For a 4-pole device on a 400 V three-phase supply, that covers the full mixed-load panel.

Depth is 70 mm, which matches the 70 mm installation depth — no extra projection beyond the rail. The 60 mm grid spacing aligns with standard distribution board cutouts. Mounting position is unrestricted, so it can go in any orientation within the enclosure.

Short-circuit and thermal performance

Rated short-circuit current withstand is 10 kA per IEC 61008-1, with a permissible series fuse short-circuit current of 100 A maximum. Power dissipation per pole is 0.8 W in hot operating state — negligible for enclosure thermal budgeting. The -25 °C lower limit covers most unheated utility rooms; if the panel sits in a freezer or exterior enclosure in a cold climate, verify the ambient stays above that.

Frequently asked questions

What is the difference between this selective RCCB and a standard instantaneous RCCB?

The selective (time-delayed) design means it withstands a brief residual current without tripping, allowing a downstream instantaneous RCD to clear the fault first. This provides discrimination — only the faulted branch drops, not the upstream feeder. The 5SV3642-8 has no short-term delayed switching function; its selectivity comes from the intentional delay characteristic built into the selective design.

Where can I buy the 5SV3642-8?

The 5SV3642-8 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What compliance documentation is available for the 5SV3642-8?

The device carries a silicon-free designation and is designed to IEC 61008-1. Overvoltage category III. For specific compliance documentation (RoHS, REACH, UL, IEC declarations), these are provided with the shipment from the authorized supply chain.

MPN