Siemens 5SV3644-8MJ — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV3644-8MJ RCCB, Type A, 40A 300mA 10kA, 4P

MPN5SV3644-8MJ

Siemens 5SV3644-8MJ, Type A residual current operated circuit breaker, 40 A, 300 mA, 10 kA, 3+N-pole, 400 V, selective, 4 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Product details

The Siemens 5SV3644-8MJ is a Type A residual current operated circuit breaker (RCCB) rated 40 A with a 300 mA trip sensitivity and 10 kA short-circuit capacity. The 3+N-pole configuration covers three-phase plus neutral on a 400 V system. The selective (S-type) designation means it delays tripping to coordinate with downstream RCCBs — useful on distribution subfeeds where you want the faulted branch to clear before the main.

The 300 mA rating is a common threshold for fire protection in commercial and industrial circuits (EN 60364-4-42). It's above the 30 mA required for personnel protection, so this device guards against insulation faults and arcing that could start a fire, not against direct shock risk. The Type A waveform detection covers pulsating DC residual currents from rectifiers and switching power supplies — typical in modern panels with VFDs, UPSs, or LED drivers.

Type A selective RCCBs of this rating go into distribution boards feeding mixed loads — lighting, socket outlets, small motor circuits, and electronic equipment. The selective delay (typically 40–150 ms) lets downstream 30 mA RCCBs trip first on a ground fault, keeping the main board live for the rest of the installation. Common in commercial buildings, industrial control panels, and infrastructure sub-distribution.

Frequently asked questions

What is the 5SV3644-8MJ used for?

It's a Type A selective residual current circuit breaker for 3-phase + neutral circuits at 400 V, rated 40 A with 300 mA trip sensitivity and 10 kA breaking capacity. Used for fire protection and ground-fault coordination in distribution boards.

Where can I buy the 5SV3644-8MJ?

This part is sourced and quoted to order against an RFQ. Current pricing and availability are confirmed at quote time through our distribution network.

What does Type A and selective mean on this RCCB?

Type A detects pulsating DC residual currents from rectified loads (VFDs, switched-mode supplies). Selective (S-type) introduces a deliberate trip delay so a downstream RCCB clears first during a fault, keeping upstream circuits live.