Skip to main content
Siemens 5SV3646-6BA — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SV3646-6BA RCCB, 4P, 63 A, 300 mA, Type A

MPN5SV3646-6BA

Siemens SENTRON RCCB, 4-pole, Type A, 63 A rated at 40 °C, 300 mA residual trip, 10 kA SCCR, DIN-rail mount, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SV3646-6BA — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SV3646-6BA — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV3646-6BA — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV3646-6BA — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SV3646-6BA — Electrical
ParameterValue
Operational current / at AC / rated value63 A

Product details

RCCB for 230/400 V AC networks — Type A, 63 A, 300 mA

The Siemens SENTRON 5SV3646-6BA is a 4-pole residual current circuit breaker (RCCB) designed for 230/400 V AC supply, rated 63 A at 40 °C and tripping on a 300 mA residual current. Rated short-circuit capacity is 10 kA per IEC 61008-1, with a conditional rating of 0.8 kA under EN 60898.

Depth is 70 mm. Silicon-free construction avoids outgassing issues in coating or potting processes.

Thermal derating and selectivity

Rated current holds at 63 A from 40 °C through 60 °C ambient. At 65 °C it derates to 57.35 A; at 70 °C to 48.84 A. The flat thermal curve up to 60 °C gives headroom in warm panels — no need to oversize for typical enclosure temperatures. Permissible let-through energy is 110 000 A²·s, and surge current withstand is rated at 1 kA. These figures support coordination with upstream MCBs — the RCCB will ride through short-duration surges without nuisance tripping.

Frequently asked questions

Will 5SV3646-6BA drop into a panel specified around 5SJ6325-7RC without rewiring?

No — the 5SJ6325-7RC is a miniature circuit breaker (MCB), not an RCCB. The 5SV3646-6BA is a residual current device with different function, wiring, and terminal layout. They are not drop-in interchangeable.

MPN
5SV3646-6BA